Building an Oil and Gas Testing Lab for a Utility Workshop

A utility decides to bring oil and gas testing in-house, and the first question is which tests. The answer comes from the decisions the laboratory has to support rather than from a list of available determinations. Transformer oil testing laboratory setup starts with the decisions, then the tests, then the equipment and the competence.

The pressure to bring testing in-house usually comes from turnaround. A sample sent to an external laboratory takes days; a screening result produced in the workshop takes hours, and the difference matters most in the period after an event.

Scope of a utility oil testing lab

The scope should be defined by the decisions the utility needs to take. Screening decisions, interval decisions, post-event decisions and acceptance decisions are the four categories, and they require different determinations at different frequencies.

The screening and post-event decisions are where turnaround matters most, which makes them the natural first scope. The acceptance and interval decisions are less time-critical and can be supported by external analysis for longer.

The scope should also consider the sample volume. A laboratory serving one workshop may run a handful of samples a week; one serving a regional fleet may run hundreds, and the difference changes both the equipment specification and the staffing model.

Tests to keep in-house versus outsource

Determination Case for in-house Case for outsourcing
Moisture content Frequent, quick, needed after events Where volume is very low
Breakdown voltage Frequent and quick; simple equipment Rarely worth outsourcing
Dissolved gas analysis Core screening; turnaround matters most here Where the equipment and expertise cannot be justified by volume
Acidity and interfacial tension Ageing trend, cheap to run Where only occasional
Furan analysis Where paper ageing is a regular question Usually outsourced until volume justifies it
SF6 gas analysis Where the utility operates gas-insulated equipment in quantity Where gas work is contracted out with the gas handling
Specialist determinations Rarely Almost always, until volume and competence exist

The dissolved gas determination is the one that most often decides the business case, because it is the test whose turnaround most affects the decision it supports.

Equipment list by test type

The list has four parts. The first is the instrument for each determination, with its calibration and reference requirements. The second is the sample handling equipment: the sampling apparatus, the containers, the preparation area and the storage.

The third is the reference materials and calibration standards, including the gases and reference fluids the determinations depend on. Those items have a shelf life and a supply arrangement that has to be maintained.

The fourth is the laboratory environment: the benches, the ventilation, the temperature control where the determinations require it, the waste handling and the safety equipment. That part of the list is frequently underestimated at the planning stage and accounts for a significant share of the cost.

The dissolved gas determination is usually the one that decides the case for bringing analysis in-house.

Sample reception and chain of custody

The chain of custody runs from the moment the sample is drawn to the moment the result is issued. It records who drew it, from which point, when, how it was transported and when it was received.

That record is what allows a result to be attributed to a sample and the sample to an asset. Without it, a result is a value that could belong to any unit, and its value in an investigation is limited.

The reception area should also control the condition of the samples on arrival. A sample that has been in transit for a week in a hot vehicle is a sample whose moisture result may describe the transit rather than the transformer, and the reception record should capture the condition so the result can be interpreted.

Calibration and reference materials

Each determination has its own calibration requirement, and the laboratory’s quality system depends on them being met. The calibration standards have to be traceable, in date and appropriate to the ranges in use.

Reference materials with a shelf life require stock rotation and an expiry check. A calibration gas that has passed its date produces results whose traceability cannot be demonstrated, whatever the instrument indicates.

The traceability requirements that the calibrations have to satisfy are described in the NIST handbooks, and the accreditation framework that a laboratory’s competence is measured against is described by bodies such as ILAC. The determination methods themselves are defined in the standards: the breakdown voltage method in IEC 60156 and its ASTM counterpart, the supervision guidance in IEC 60422 and the dissolved gas interpretation in IEC 60599.

Each determination brings its own calibration and reference material requirements, which the laboratory has to maintain.

Safety and waste handling

The laboratory handles oil samples, solvents, calibration gases and in some cases SF6 gas and its decomposition products. Each of those brings its own handling and waste requirements.

Ventilation is the primary control for the gas work, and it has to be designed for the determinations performed rather than for a general laboratory. The extraction arrangements for solvents and the storage of gas cylinders are part of the fit-out.

Waste handling covers the used samples, the solvents, the filter elements and any gas that is not reused. The recovered gas from SF6 work has its own handling and reporting requirements, and the re-use specification is published as IEC 60480.

Staff competence and documentation

The laboratory needs operators who are competent in the methods, not only in the instruments. That means training in the determination, the interpretation and the limitations, with an assessment and an authorisation record.

The competence should be specific to each determination. A technician trained on the breakdown voltage test is not thereby competent in dissolved gas analysis, and the authorisation record should reflect the difference.

The documentation set covers the methods, the calibration records, the sample records, the results and the quality control checks. Where the laboratory operates to an accreditation standard, that documentation is the evidence of the system; where it does not, it is still what makes the results usable.

Phasing the build-out over budget cycles

Phasing matches the investment to the workload and to the competence available. The first phase usually covers the high-frequency, quick determinations and the sample handling arrangements; later phases add the determinations that require more equipment and more skill.

The phasing should be planned so that each phase is a complete capability rather than part of one. A laboratory with the instrument for a determination but without the reference materials or the trained operator cannot produce a result.

The plan should also allow for the quality system to develop with the scope. A laboratory that introduces a determination before the system for recording and checking it exists produces results that cannot be defended, and rebuilding the system afterwards is more difficult than building it with the first phase. The equipment range for a laboratory build-out is grouped under transformer oil laboratory equipment, within the wider oil testing range, with the gas measurement instruments on the SF6 testing hub.

A laboratory is scoped by the decisions it has to support, not by the tests it could perform.

Send your sample volume, asset fleet and the decisions you need in-house to our engineering team and we will help you scope the phases and the equipment list. Laboratory instruments are grouped under transformer oil laboratory equipment.

FAQ

What determines the scope of a utility oil testing lab?

The decisions the utility needs to take in-house. Screening tests that determine whether a unit needs attention are usually the first to bring in; specialised determinations that need equipment and expertise beyond the workload stay outsourced. The scope follows the decision, not the test menu.

Which tests should be kept in-house?

Those performed frequently, those whose turnaround matters, and those that need to be repeated quickly after an event. Dissolved gas analysis, moisture content, breakdown voltage and acidity are the usual core. Determinations that require specialist equipment and are performed rarely are usually better outsourced.

What does the equipment list look like?

One item per determination, plus the sample handling equipment, the reference materials and the calibration standards. The list should also include the reception area, the storage for samples awaiting analysis, the waste handling and the environmental control for the room, because those determine whether the results are usable.

How is the chain of custody handled?

With a record from the moment the sample is drawn to the moment the result is issued: who drew it, from where, when, how it was transported, when it arrived and who received it. That record is what allows a result to be attributed to a sample and the sample to the asset.

Should the build-out be phased?

Usually yes. Phasing matches the investment to the workload and to the competence available, and it allows the first phase to establish the laboratory’s quality system before the scope expands. Attempting the full scope at once tends to produce equipment without operators trained on it.

Recommended

  • Breaker Maintenance Testing Schedules: What Changes With Duty CycleKnowledge
  • Dissolved Gas Analysis: Reading Ratios Without OverdiagnosingKnowledge
  • Cable Acceptance Testing Programmes for New InstallationsKnowledge
  • Insulation Resistance Testing: Test Voltage Selection by AssetKnowledge
  • Partial Discharge Pattern Recognition: Separating Defects From NoiseKnowledge
  • DC System Commissioning: Battery, Charger and Protection CoordinationKnowledge

By hvhipot