DC high voltage generator acceptance

DC high voltage generator is also called high voltage generator, intermediate frequency DC high voltage generator and high voltage DC generator for short.

Main Specifications

1. Output voltage polarity: negative polarity

2. Working power

DC high voltage generator is also called high voltage generator, intermediate frequency DC high voltage generator and high voltage DC generator for short.

Precautions during acceptance:

1. The technical data should be complete, including instructions, certificates, test reports, maintenance record cards, etc.

2. The nameplate identification should be obvious and firm, including the name of the instrument, manufacturer, model, number, accuracy, measurement range, date of manufacture, etc.

3. Both the control box of the DC high voltage generator and the high voltage part must have a clearly marked ground terminal

The output voltage of the DC high voltage generator should be able to be boosted from zero, continuously and smoothly adjustable, and the adjustment fineness of the output voltage should be better than 0.1% of the rated voltage value. The output voltage adjustment knob of the DC high voltage generator should have a zero lock function , In order to prevent the adjustment knob is no longer zero.