The measured resistance is too large

The reason and solution for the large resistance value of the earth grid grounding resistance measurement, the method of using the grounding resistance tester and the function of the earth network, the reason and solution for the large resistance value of the earth grid grounding resistance measurement come from the power detection test Technology, taking into account the power of the power to establish research and development standards, stable and safe power test equipment.

The role of the ground network

The grounding grid in the power system plays a vital role in ensuring the safety of personnel and equipment. When the grounding resistance of the grounding grid is greater than the qualified standard value, the personal safety and the operation of the equipment will be endangered. Therefore, it is necessary to analyze the reason why the measured resistance value of the grounding resistance is too large, and take effective technical measures to reduce the grounding resistance value to within the qualified standard value.

Reasons and solutions for high resistance

Since the ground grid is buried in the soil, the ground resistance is directly related to the soil composition, temperature and humidity. That is to say, the soil resistivity affects the magnitude of the ground resistance value. The soil resistivity is an important data for grounding network design. We can use a ground resistance tester to measure the resistivity of this piece of soil. If the soil resistivity is too large, we can improve the soil. Soil resistance reducers or water can be used to maintain the contact between the soil and the ground net.

The method of measuring the grounding resistance of the ground grid is also the main reason for the large resistance. When measuring, we should clearly know the length of the diagonal of the ground grid, because the measuring current line length of the earth grid grounding resistance tester is 3~5 times the length of the diagonal line of the ground grid, and the measuring voltage line is 0.618 times the current line. ,

The rust on the ground pile is cleaned, and the buried depth is greater than 0.5 meters. At the same time, check whether the connection between the test line and the ground pile is conducted. The current test line and the voltage test line are connected to the instrument according to the specified length and discharged in parallel. The other end is connected to the two ground stakes. After the wiring is completed, the instrument can directly press the test key to measure the grounding resistance value. The instrument will automatically eliminate wiring errors during measurement based on the fHV Hipot Electric Co., Ltd.-pole method.

Good grounding is not only for safety, but also to prevent damage to electrical equipment. Good grounding will improve the reliability of the equipment and reduce the possibility of damage caused by lightning or fault current.