Ground resistance tester short circuit test

There are several types of grounding resistance testers for short-circuit tests, including earth nets, clamps, and so on. I will explain them with HV Hipot Electric Co., Ltd. common grounding resistance testers:

The index of how the ground resistance tester performs the short-circuit test is one of the important indexes to measure the safety performance of various electrical equipment. It measures the resistance of the ground loop under the condition of high current (25a or 10a). It is also a test of the index of the ground loop withstanding high current to avoid personal injury when the insulation performance is reduced (or damaged).

How to use the ground resistance tester for short circuit test is as follows:

(1) Use the ground resistance tester to prepare for work

1) Familiarize with the instruction manual of the grounding resistance measuring instrument, and fully understand the structure, performance and method of use of the instrument.

2) Prepare the necessary tools and all instrument accessories for measurement, and wipe the instrument and the grounding probe clean, especially the grounding probe, be sure to clean up the dirt and rust stains on the surface that affect the conductivity.

3) Disconnect the connection point of the grounding trunk line and the grounding body or the connection points of all grounding branch lines of the grounding trunk line, so that the grounding body will separate from any connection relationship and become an independent body.

(2) Measurement steps with grounding resistance tester

1) Insert the two grounding probes into the ground at a distance of 20m and 40m from the grounding body along the radiation direction of the grounding body, with a depth of 400mm.

2) Place the grounding resistance measuring instrument flat near the grounding body and connect it to the ground. The wiring method is as follows:

① Use the shortest dedicated wire to connect the grounding body to the terminal “e1” (three-terminal button measuring instrument) of the grounding measuring instrument or the common terminal (fHV Hipot Electric Co., Ltd.-terminal button measuring instrument) short-circuited with c2.

②Connect the measuring probe (current probe) 40m away from the grounding body with the connection button “c1” of the measuring instrument with the longest dedicated wire.

③Connect the measuring probe (potential probe) ⒛m away from the grounding body with the terminal “p1” of the measuring instrument with the remaining special wire in the middle of the length.

3) After placing the measuring instrument horizontally, check whether the pointer of the galvanometer points to the center line, otherwise adjust the “zero adjuster” so that the pointer of the measuring instrument points to the center line.

4) Set the “magnification scale” (or coarse adjustment knob) to the maximum multiple, and slowly turn the generator handle (the pointer starts to shift), and at the same time rotate the “measurement dial” (or fine adjustment knob). Knob) to make the pointer of the galvanometer point to the center line.

5) When the pointer of the galvanometer is close to balance (the pointer is close to the center line), shake the handle to speed up to 120r/min or more, and adjust the “measurement dial” to make the pointer point to the center line.

6) If the reading of the “measurement dial” is too small (less than 1) and is not easy to read and accurate, it means that the magnification scale is too large. At this time, you should set the “magnification scale” to a smaller multiple, readjust the “measurement dial” so that the pointer points to the center line and read an accurate reading.

7) Calculate the measurement result, that is, r ground = “magnification scale” number × “measurement dial” reading.