What is the standard for impulse test?

The Impulse Voltage Test System under HV Hipot Electric Co., Ltd. can help many power workers conduct various power tests more conveniently.

1. Electrical Equipment and Insulation Materials (High-Voltage Engineering)

Core Standards:

IEC 60060-1: *High-voltage test techniques �C Part 1: General definitions and test requirements* �C The foundational standard defining parameters for high-voltage test waveforms (including lightning/ switching impulses), tolerances, test procedures, and measurement system requirements.

IEC 60255-27: Measuring relays and protection equipment �C Part 27: Product safety requirements �C Includes insulation tests (e.g., impulse voltage tests) for protective relays.

IEC 62271-1: *High-voltage switchgear and controlgear �C Part 1: Common specifications* �C Specifies insulation tests (lightning/switching impulse) for switchgear, circuit breakers, etc.

IEEE Std 4: IEEE Standard for High-Voltage Testing Techniques �C Widely used in North America, analogous to IEC 60060-1.

Key Pulse Waveforms:

Standard Lightning Impulse (LI): 1.2/50 μs (wavefront time ~1.2 μs, time-to-half-value ~50 μs). Simulates lightning overvoltage.

Standard Switching Impulse (SI): 250/2500 μs or wavefront ≥100 μs / time-to-half-value ≥1000 μs. Simulates switching overvoltage.

Chopped Lightning Impulse: LI truncated at 2�C5 μs to simulate insulation flashover/arrester operation.

Test Requirements:

Withstand Test: Equipment withstands specified impulses without destructive discharge.

Disruptive Discharge Test: Determines breakdown voltage (e.g., 50% disruptive discharge voltage, U₅₀).

Measurement System: Must comply with IEC 60060-2/IEEE Std 4.

Environment: Tests performed under standard atmospheric conditions (with corrections for temperature/humidity).

2. Electronic Equipment and Components (Electromagnetic Compatibility – EMC)

Core Standards:

IEC/EN 61000-4-4: *Electromagnetic compatibility (EMC) �C Part 4-4: Testing and measurement techniques �C Electrical fast transient (EFT)/burst immunity test* �C Evaluates immunity to fast transients (e.g., from relays/switches). Waveform: 5/50 ns bursts.

IEC/EN 61000-4-5: *EMC �C Part 4-5: Testing techniques �C Surge immunity test* �C Tests immunity to surges (lightning/switching transients). Key waveforms:

Combination Wave: 1.2/50 μs (open-circuit voltage) & 8/20 μs (short-circuit current).

Communication Line Surge: 10/700 μs for long-distance lines.

ISO 7637-2: Road vehicles �C Electrical disturbances from conduction and coupling �C Part 2: Electrical transient conduction along supply lines �C Defines automotive transient pulses (e.g., Pulse 1, 2a, 3a/b) for immunity testing.

Test Requirements:

Immunity Test: Performance must remain within manufacturer-defined criteria (Criteria A/B/C) during/after pulse application.

Application: Pulses applied to power/signal lines via coupling networks.

Severity Levels: Voltage/current amplitudes selected based on operational environment.

3. Communication and Signal Systems

Standards may reference IEC 61000-4-5 or define specific cable tests (e.g., telecom lines, coaxial cables) for induced surges. Telecommunication standards (e.g., ITU-T K-series) include surge protection requirements.

4. Specific Components

Semiconductors (TVS diodes, varistors): IEC 61643-311 defines pulse withstand tests (8/20 μs current, 1.2/50 μs voltage).

Capacitors/Transformers: Product-specific standards (e.g., IEC) include impulse tests for insulation/self-healing verification.

 

By hvhipot