What is a series resonance test device

HV Hipot Electric Co., Ltd. specializes in producing series resonance (also known as variable frequency series resonance complete equipment). Next, we will share with you what is a series resonance test device?

What is a series resonance test device:

It is generally composed of a variable frequency power supply, excitation transformer, reactor, and capacitive voltage divider. The capacitor and reactor of the test sample form a series resonant connection; The voltage divider is connected in parallel to the test sample to measure the resonant voltage on the test sample and provide an overvoltage protection signal. Mainly used for conducting AC voltage withstand tests.

Main features and advantages:

1. The required power capacity is greatly reduced. The series series series resonance test device uses resonant reactors and the capacitance of the test object to generate resonance, thereby obtaining the required high voltage and high current. In the entire system, the power supply only needs to provide the active consumption part of the system. Therefore, the required power supply for the test is only 1/Q times the test capacity (Q is the quality factor).

2. The weight and volume of the equipment have been greatly reduced. In a series resonant power supply, not only is the bulky high-power voltage regulating device and ordinary high-power power frequency test transformer eliminated, but the resonant excitation power supply only requires 1/Q of the test capacity, greatly reducing the system weight and volume, usually 1/5 to 1/10 of ordinary test devices.

3. Improve the output voltage waveform. A resonant power supply is a resonant filtering circuit that can improve the waveform distortion of the output voltage, obtain a good sine wave, and effectively prevent the false breakdown of the test sample caused by harmonic peaks.

4. Prevent large short-circuit currents from burning the fault point. In the resonant state, when the weak point of the insulation of the test sample is broken down, the circuit immediately becomes detuned (capacitance changes, not meeting the resonance condition), and the circuit current rapidly decreases to 1/Q of the normal test current. However, when using parallel resonance or traditional test transformers for AC withstand voltage testing, the breakdown current immediately increases by tens of times. Compared with the two, the short-circuit current is hundreds of times different from the breakdown current. So, series resonance can effectively identify insulation weaknesses without the concern of large short-circuit currents burning the fault point.

5. There will be no overvoltage recovery. When the test sample experiences breakdown and flashover, due to the loss of resonance conditions, the high voltage immediately disappears, the arc is immediately extinguished, the protective circuit of the device is activated, and the output is cut off.

By hvhipot