Battery Condition Monitoring: Data You Can Act On

A monitoring system can measure every cell in a substation battery every few minutes and produce more data in a week than a maintenance team will read in a year. The problem with battery condition monitoring substation installations is rarely the measurement. It is the absence of thresholds, reporting and responses that turn the data into a decision.

The measurements themselves are the same quantities a technician would take on a visit: cell voltage, string voltage, current, temperature and, on many systems, an impedance or conductance value per cell. Monitoring changes the frequency of the measurement, not its nature.

What monitoring actually measures

Cell or block voltage is the fundamental measurement. It responds to a cell that is failing to charge, one that is self-discharging, and one whose internal resistance is causing it to fall further than its neighbours under load.

String voltage and current establish the operating state and allow the cell measurements to be interpreted. Without the current, a voltage reading cannot be related to the load the battery was carrying at the time.

Temperature at one or more points indicates the thermal environment. A cell whose temperature differs from its neighbours is a cell with an internal condition, and the temperature measurement is often the earliest indicator of a problem that impedance would show later.

Impedance or conductance per cell, where the system includes it, provides the screening quantity that a manual visit would produce. Taken continuously, it gives the trend rather than a point.

Data quality and where it fails

Failure How it appears Consequence
Sensor drift One cell reading slowly diverges from its neighbours with no physical cause A false alarm, and eventually distrust of the whole system
Connection resistance A reading that reflects the sense connection rather than the cell Misattribution of a fault to the cell
Unrecorded conditions Cell values without the current and temperature at the time Data that cannot be interpreted when an alarm occurs
Sampling too infrequent An event between samples is not captured The monitoring misses the condition it was installed for
System status not reported A period with no data is indistinguishable from a quiet period A failed sensor looks like a healthy battery

The last row is the one that undermines confidence. A system that does not report its own health cannot be relied on, because the absence of alarms may mean the battery is healthy or may mean the monitoring has stopped.

Actionable thresholds versus noise

An actionable threshold produces an alert that leads to a defined response. A noisy threshold produces alerts that are ignored, which is worse than no threshold because it consumes attention without producing a decision.

Thresholds set from the string’s own behaviour work better than generic figures. A cell that departs from the string median by more than a defined proportion, a cell whose impedance has moved by more than a defined proportion from its own history, and a string whose voltage falls faster than its discharge profile predicts are all criteria that relate to the specific installation.

Each criterion should have a defined response attached: remeasure, inspect the connection, bring the capacity test forward, or schedule a replacement. A threshold without a response is a notification rather than a control.

A threshold that produces an alert without a defined response consumes attention without producing a decision.

Integrating monitoring with periodic tests

Monitoring and periodic testing answer different questions. Monitoring identifies cells that have changed; the capacity test establishes what the string can deliver. Neither substitutes for the other.

The integration works best when the monitoring data determines the timing of the periodic test. A string whose monitoring shows a widening spread is a candidate for an earlier capacity test, and the screening result makes the discharge test more informative because the cells to watch are already identified.

The integration also works in the other direction. The capacity test produces the individual cell voltages under discharge, which are the most direct evidence available about the weakest cell. Those values are what allow the monitoring thresholds to be set from a real discharge rather than from an assumed profile.

Reporting that operations will use

The report should present the string as a whole with the exceptions identified, rather than the data for every cell. An operations team needs to know which cells require attention and what the recommended action is, not the value of every measurement.

The exceptions should be ranked by severity and accompanied by their trend. A cell that has moved slightly over a year is different from one that has moved the same amount in a week, and the reporting should make that difference visible.

The report should also state the health of the monitoring system itself, including any period during which data was missing. That statement is what allows the reader to judge whether an absence of alarms means anything.

The manual screening visit produces the same quantity as the monitoring system, which is what makes the two comparable.

Cost and maintenance of the monitoring layer

The monitoring layer has a capital cost and a continuing cost. The capital cost includes the sensors, the wiring or the wireless infrastructure and the installation, which on an existing battery involves working on a live DC system and re-terminating connections.

The continuing cost includes the data handling and the review of alerts. That cost is often underestimated: a system that produces alerts nobody reviews has no value, and a system that produces alerts somebody reviews consumes staff time in proportion to the number of alerts.

The maintenance of the monitoring system itself is a third cost. Sensors, connections and communication equipment all require attention, and the standard of that attention should be defined in the specification rather than assumed.

When monitoring is not worth it

Monitoring is not worth installing where the battery is small, non-critical, readily replaced or easy to test on a short visit. In those cases a periodic screening programme provides similar protection at a fraction of the cost.

It is also not justified where nobody is able to act on the alerts. A monitoring system installed in an unmanned substation whose data goes to an office that does not review it produces a record rather than a control, and the record could have been produced by periodic visits.

The decision should be made per battery or per battery class, on the consequence of an undetected failure. Where that consequence is contained, the money is better spent on screening more of the fleet.

Specifying a monitoring system

The specification should state what is measured per cell and per string, the sampling interval, the accuracy of each measurement, the thresholds and their configurability, the alarm and reporting outputs, and the health reporting of the system itself.

It should also state the installation requirements, which on an existing battery involve the DC system arrangements, the wiring route and the interaction with the existing protection and alarm scheme. Those arrangements are part of the work and should be priced as such.

Finally, the specification should state the data ownership and export requirements. The owner’s maintenance records have to remain usable if the monitoring vendor changes. The requirements for stationary lead-acid batteries are published as IEC 60896-21 and IEC 60896-22; instrument method documentation is published by suppliers such as Hioki and Fluke; research into battery condition assessment is published by EPRI; utility practice is coordinated through CIGRE study committees; and the instrument range is grouped on the DC system and battery testing hub.

A monitoring system that reports every cell but no exceptions will not be read.

Send your battery types, string sizes and the consequence of failure for each to our engineering team and we will help you set thresholds and a reporting format. Battery monitoring and screening instruments are grouped on the DC system and battery testing hub.

FAQ

What does a monitoring system actually measure?

Typically the voltage of each cell or block, the string voltage and current, the temperature at one or more points, and often an impedance or conductance value taken periodically per cell. Some systems add electrolyte level or specific gravity on vented cells. The measurements are the same quantities a technician would take on a visit, recorded continuously instead of at intervals.

Where does monitoring data usually fail?

In the interpretation rather than the measurement. A system that produces a value per cell every hour generates a volume that nobody reviews, and an alarm that fires on a value drifting near a limit is ignored after the third occurrence. The failure is the absence of thresholds and reporting that relate the data to a decision.

How should thresholds be set?

From the string’s own behaviour rather than from a generic figure. A cell that departs from the string median by more than a defined proportion, a cell whose impedance has moved by more than a defined proportion from its own history, and a string whose voltage falls faster than its discharge profile predicts are all actionable criteria. Each should lead to a defined response.

Does monitoring replace periodic testing?

No. Monitoring identifies cells that have changed; it does not measure the capacity the string can deliver. The capacity test remains the measurement that establishes whether the battery still meets its design duty, and the monitoring data is what determines when to bring that test forward.

When is monitoring not worth installing?

Where the battery is small, non-critical, readily replaced or easy to test on a short visit. The capital and maintenance cost of a monitoring layer is justified by the consequence of an undetected failure, and where that consequence is contained the money is better spent on a periodic screening programme.

Recommended

  • Why Resonant AC Testing Is Used for Generator StatorsKnowledge
  • Proof Test vs Diagnostic Test: What Each One Can Tell YouKnowledge
  • Cable Acceptance Testing After Installation: Building the Test ProgrammeKnowledge
  • What to Look For in a Hipot Tester: Safety Features, Interlocks and Output ControlKnowledge
  • How to Interpret Hipot Test Failures and Leakage Current ReadingsKnowledge
  • How to Match Portable Hipot Test Set Ratings to Site RequirementsKnowledge

By hvhipot