Cable AC Resonance Testing System and Reactor

The AC Resonance Test System under HV Hipot Electric Co., Ltd. power can help many power workers conduct various power tests more conveniently.

600kVA/120kV Cable AC Resonance Testing System Reactor Usage Relationship Table

Electric motor, generator, AC withstand voltage test, capacitance range 0.0555~0.111uf, test frequency 60Hz, test voltage 120kV.

Take a frequency of 60Hz

I=2πfCUtest=2π×60×0.111×10-6×120×103=5.0 A

Related reactor inductance L==1/ω 2C=63.4H

Based on the above test voltage, current, frequency, and inductance, design 12 series cable AC resonance test system reactors to meet the above test requirements and objectives, with a single reactor of 50kVA/20kV/2.5A/21H

Verification 1.

Electric motor, generator, AC withstand voltage test, capacitance range 0.0555uF, test frequency 60Hz, test voltage 120kV.

When 6 reactors are connected in series in the cable AC resonance testing system, the inductance is 21 * 6=126H

Test frequency f=1/2 π√ LC=1/(2 × 3.14 × √ 126 × 0.0555 × 10-6)=60.2Hz

Test current I=2 π fCUTEST=2 π × 60.2 × 0.0555 × 10-6 × 120 × 103=2.5A

Verification 2.

Electric motor, generator, AC withstand voltage test, capacitance range 0.111uF, test frequency 60Hz, test voltage 120kV.

When 6 reactors are connected in series and 2 groups are connected in parallel, the inductance is (21 * 6)/2=63H

Test frequency f=1/2 π√ LC=1/(2 × 3.14 × √ 63 × 0.111 × 10-6)=60.2Hz

Test current I=2 π fCU Test=2 π × 60.2 × 0.111 × 10-6 × 120 × 103=5.0A

Conclusion: The device capacity is 600kVA/120kV; 12 reactors, each with a capacity of 50kVA/20kV/2.5A/21H, can meet the testing requirements when used in combination.