Common failures of switch loop resistance tester

Common faults and solutions of the switch loop resistance tester:

1. Failure phenomenon 1 of the switch loop resistance tester

The test current of the loop resistance tester is normal, and the micro-ohm value bit displays “1”;

the reason:

The position of the voltage clamp is wrong. The resistance of the tested loop exceeds 2000. The voltage signal line is broken or not connected. ;

elimination method:

Handle the voltage signal circuit, and clamp the voltage clamp. When the range is exceeded: use a multimeter to measure the voltage values of P1 and P2, and the resistance value = voltage value/current value.

2. Failure phenomenon of switch loop resistance tester 2

Press the “test switch” on the switch loop resistance tester, the ammeter will display no current, and the micro-ohm meter will display “1”;

the reason:

The 100A current loop is not connected properly. The subject switch is not closed;

elimination method:

Check the test line, reconnect, and re-clamp. Close the switch.

3. Failure phenomenon three of the switch loop resistance tester

The switch loop resistance tester is connected to 220V AC power supply, the fan is silent, and the “test switch” is clicked, the ammeter and micro-ohm meter have no display;

the reason:

The 220V AC power supply fails, and the fuse is not installed or is fused;

elimination method:

Check and rule out. (100A instrument insurance is not less than 6A, and then contact the factory to solve it. (Never connect to DC or 380V AC power)

After the switch loop resistance tester fails, the correct operation method is to interrupt the test work, disconnect the test product, and cut off the power supply. After the equipment is trouble-free, the inspection and test work will be performed again.

Avatar photo

By hvhipot